# Pythia Technologies CM03A: Modbus and BACnet Register List Written for AI assistants and integrators. Revision 2026-11-19. Section tags in square brackets, such as [CMR-4], match the PDF register list (PTECH_RegisterList_CM03A.pdf). Technical support: 740-363-2272, support@pythiatech.com. Contact us for pricing. ## [CMR-1] About the CM03A The CM03A is a 22-input I/O module. Every input is universal and can be set up as: - a dry contact, normally open (NO) or normally closed (NC) - a 10K Type II thermistor, read in °C or °F - a 0 to 5 VDC signal - a 0 to 10 VDC signal The CM03A reports its inputs to a building management system, a Pythia DM or any Modbus or BACnet master: | Port | Protocols | |---|---| | Ethernet | Modbus TCP, BACnet/IP | | RS-485 | Modbus RTU, BACnet MS/TP | Power is 12 to 24 VAC or VDC. Wiring, mounting and the setup software are covered in the CM03A quick start guide (PTECH_Guide_CM03A.pdf). ## [CMR-2] Factory defaults | Setting | Default | Register | |---|---|---| | IP address | 169.254.254.1 | 40063 to 40066 | | Subnet mask | 255.255.0.0 | 40067 to 40070 | | Gateway | 169.254.254.254 | 40071 to 40074 | | DHCP | Off | 40062 | | Modbus address | 2 | 40007 | | RS-485 | 19200 baud, 8 data bits, no parity, 1 stop bit (8N1) | 40016 | | BACnet/IP UDP port | 47808 | 40039 | | Every input | Dry contact, normally open | 40226 to 40247 | ## [CMR-3] How to read this list - Every register is a 16-bit **holding register**. Read with function code **3** (Read Holding Registers). Write with function code **6** (Write Single Register). - Register numbers use the common 4xxxx style: **40001 is the first holding register**. Some masters ask for an offset from 0 instead; in that case subtract 40001 (register 40101 is offset 100). - **R** means read only. **R/W** means you can read and write it. - Values are whole numbers with no scaling unless the list says otherwise. > **Tip:** Read a block of registers in one request rather than one at a time. All 22 input values are 44 registers starting at 40101. ## [CMR-4] Device and network registers | Register | Name | Access | Values and default | |---|---|---|---| | 40001 to 40004 | Serial number | R | Four registers | | 40005 | Firmware version | R | | | 40007 | Modbus address | R/W | 1 to 254. Default 2 | | 40008 | Model | R | 43 = CM03A | | 40009 | Hardware version | R | | | 40016 | RS-485 baud rate | R/W | 0 = 9600, 1 = 19200. Default 1 (19200) | | 40022 | RS-485 protocol | R | The protocol in use on the RS-485 port | | 40039 | BACnet/IP UDP port | R/W | Default 47808 | | 40062 | DHCP | R/W | 0 = off (fixed address), 1 = on. Default 0 | | 40063 to 40066 | IP address | R/W | One part per register. Default 169 / 254 / 254 / 1 | | 40067 to 40070 | Subnet mask | R/W | One part per register. Default 255 / 255 / 0 / 0 | | 40071 to 40074 | Gateway | R/W | One part per register. Default 169 / 254 / 254 / 254 | | 40077 | Apply network settings | W | Write 1 to apply the new network settings and restart | > **Important:** New IP address, mask, gateway and DHCP values take effect only after you write 1 to register 40077. Write all of them first, then 40077. Write the new address down before you apply it: the module answers at the new address after it restarts. ## [CMR-5] Input values Each input has a **32-bit signed value** held in two registers, high word first: - Input n high word: register 40101 + 2 × (n − 1) - Input n low word: register 40102 + 2 × (n − 1) Value = high word × 65536 + low word, read as a signed 32-bit number. The CM03A does not scale the value. A dry-contact input reads 0 or 1. The full map for all 22 inputs is in [CMR-7]. > **Tip:** Many masters have a "32-bit integer, big-endian" or "ABCD" data type. Use that and point it at the high-word register. ## [CMR-6] Input configuration Each input has three settings. Set them with the CM03A setup software or by writing the registers. **Range** (register 40225 + n). Default 12. | Code | Range | Set Type to | |---|---|---| | 0 | Not used | | | 1 | Dry contact, normally closed (NC) | 0 (Digital) | | 12 | Dry contact, normally open (NO) | 0 (Digital) | | 3 | 10K Type II thermistor, °C | 1 (Analog) | | 4 | 10K Type II thermistor, °F | 1 (Analog) | | 11 | 0 to 5 VDC | 1 (Analog) | | 19 | 0 to 10 VDC | 1 (Analog) | **Soft switch** (register 40247 + n): 0 = AUTO, 1 = MAN. Leave it at 0 (AUTO) for normal monitoring. **Type** (register 40269 + n): 0 = Digital, 1 = Analog. ## [CMR-7] Register map for all 22 inputs The value is two registers (high / low). BACnet is the matching Binary Input object ([CMR-9]). | Input | Value (high / low) | Range | Soft switch | Type | BACnet | |---|---|---|---|---|---| | 1 | 40101 / 40102 | 40226 | 40248 | 40270 | BI1 | | 2 | 40103 / 40104 | 40227 | 40249 | 40271 | BI2 | | 3 | 40105 / 40106 | 40228 | 40250 | 40272 | BI3 | | 4 | 40107 / 40108 | 40229 | 40251 | 40273 | BI4 | | 5 | 40109 / 40110 | 40230 | 40252 | 40274 | BI5 | | 6 | 40111 / 40112 | 40231 | 40253 | 40275 | BI6 | | 7 | 40113 / 40114 | 40232 | 40254 | 40276 | BI7 | | 8 | 40115 / 40116 | 40233 | 40255 | 40277 | BI8 | | 9 | 40117 / 40118 | 40234 | 40256 | 40278 | BI9 | | 10 | 40119 / 40120 | 40235 | 40257 | 40279 | BI10 | | 11 | 40121 / 40122 | 40236 | 40258 | 40280 | BI11 | | 12 | 40123 / 40124 | 40237 | 40259 | 40281 | BI12 | | 13 | 40125 / 40126 | 40238 | 40260 | 40282 | BI13 | | 14 | 40127 / 40128 | 40239 | 40261 | 40283 | BI14 | | 15 | 40129 / 40130 | 40240 | 40262 | 40284 | BI15 | | 16 | 40131 / 40132 | 40241 | 40263 | 40285 | BI16 | | 17 | 40133 / 40134 | 40242 | 40264 | 40286 | BI17 | | 18 | 40135 / 40136 | 40243 | 40265 | 40287 | BI18 | | 19 | 40137 / 40138 | 40244 | 40266 | 40288 | BI19 | | 20 | 40139 / 40140 | 40245 | 40267 | 40289 | BI20 | | 21 | 40141 / 40142 | 40246 | 40268 | 40290 | BI21 | | 22 | 40143 / 40144 | 40247 | 40269 | 40291 | BI22 | ## [CMR-8] Examples **Read input 5.** Function code 3, start at register 40109, count 2. If the reply is 0 and 1, the value is 1. **Read all 22 inputs at once.** Function code 3, start at register 40101, count 44. **Set input 3 to a 10K thermistor in °F.** Function code 6: write 4 to register 40228 (range), then write 1 to register 40272 (type). **Set input 10 to 0 to 10 VDC.** Function code 6: write 19 to register 40235, then 1 to register 40279. **Give the module a new fixed IP address, 192.168.1.50 / 255.255.255.0, gateway 192.168.1.1.** 1. Write 0 to register 40062 (DHCP off). 2. Write 192, 168, 1 and 50 to registers 40063 to 40066. 3. Write 255, 255, 255 and 0 to registers 40067 to 40070. 4. Write 192, 168, 1 and 1 to registers 40071 to 40074. 5. Write 1 to register 40077. The module restarts at 192.168.1.50. **Change the Modbus address to 5.** Function code 6: write 5 to register 40007. Use the new address from the next request on. ## [CMR-9] BACnet objects Each input is also a BACnet **Binary Input** object (object type 3). The instance number is the input number. | Object | Instance | Name | |---|---|---| | BI1 to BI22 | 1 to 22 | Input 1 state to Input 22 state | - Present Value is the state of the input: active or inactive. - BACnet/IP uses the UDP port in register 40039, default 47808. - For the BACnet device instance and BACnet MS/TP settings, call technical support at 740-363-2272.